Overview
The Xsafe fixed gas detection system has been specifically designed to meet your requirements. The dangers presented by toxic and flammable gases as well as oxygen deficiency vary with each application.
Xsafe is a non-certified low cost catalytic bead type gas detection system with 3-wire 4-20mA or mV bridge output.
Specifications
Size |
156 x 166 x 111mm (6.1 x 6.5 x 4.3 inches) |
Weight |
1kg (2.2lbs) |
Enclosure material |
Aluminium |
Ingress protection |
IP65 |
Cable entries |
1 x M20, 1/2 “NPT or 3/4 NPT* on right-side |
Terminations |
0.5 to 2.5mm2 |
Sensor type |
Catalytic bead |
Operating temperature |
mV: -40 to +80°C (-40 to 176°F)
mA: -40 to +55°C (-40 to 131°F) |
Storage |
-25°C to +65°C (-13°F to +149°F) |
Humidity |
10 to 95% RH |
Repeatability Zero drift |
<2% FSD (Typical)
<2% FSD per Month (Typical) |
Response time |
T90 <15s (Typical) |
OPerating voltage |
mA: 10-30V dc
mV: 2.0V dc |
Power requirements |
mA: 50mA at 24V dc 1.2W
mV: 300mA (Typical) |
Electrical output |
mA: 3- wire 4-20mA (current sink or source)
mV: 3- wire mV bridge
Typical signal: 12-15mV/ %LEL CH4 |
Approvals |
Not certified for use in hazardous environments
Safe area only |
EMC compliance |
EN 50270
FCC Part 15
ICES- 003 |
*3/4 ” cable entry only available on aluminium juntion boxes.
Accessories
Below is a small selection of the accessories available for the Xsafe.
Spray deflector
C01052
For outdoor installations and protection from water sprays, for example in water treatment or food processing plants. Includes accessory adaptor. (Not suitable for use with Xgard Type 4)
Sun shield
C011063
Protects against excessive heat build-up due to direct sunlight.
Supplied with fixing rivets.
Collector Cone
C01051
For aiding detection of light gases such as methane. 38cm/15″ Dia. Includes accessory adaptor.
Weatherproof cap
C01442
For offshore or other extremely wet environments. Includes accessory adaptor. (Not suitable for use with Xgard Type 4)
Flow adaptor
C01339
For use where a gas sample is being piped to the detector.
Calibration adaptor
C03005
To enable calibration gas to be applied to the detector. One adaptor can be used for several detectors.
Duct mounting kit
S011918
Allows sampling within tubes and ducts. Stainless steel plate with 6mm remote calibration fitting. Maximum duct airflow: 6 metres per second. (Not compatible with Stainless Steel Xgard or Xgard Type 4.)